Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 674952 - Burn - Electrical Fault In Electrical Box

Accident: 674952 -- Report ID: 0454510 -- Event Date: 06/21/1988
InspectionOpen DateSICEstablishment Name
10547742606/22/19883562Ina Bearing Co., Inc., Plant #4
THE PLANT ELECTRICIAN FOR A MANUFACTURING PLANT WAS CONNECTING POWER TO A ROYAL MASTER ROLL GRINDER AT A BUS DUCT DISCONNECT BOX. THE DISCONNECT BOX WAS CONNECTED TO A 600-VOLT BUS 12 FEET ABOVE THE FLOOR. ALL THE WIRING AND CONDUIT HAD BEEN INSTALLED EXCEPT FOR THE WIRING GOING INTO THE DISCONNECT BOX. A WATER PIPE HAD BEEN INSTALLED IN FRONT OF THE DOOR OF THE BOX SO THAT ITS DOOR COULD OPEN ONLY UP TO A 45 DEGREE ANGLE. THE DISCONNECT WAS IN THE OFF POSITION, AND ALL FUSES HAD BEEN REMOVED. THE ELECTRICIAN WAS STANDING ON AN ELEVATED POWER LIFT INSTALLING THE GROUNDING CONDUCTOR TO ITS CONNECTION IN THE BOX WHEN AN ELECTRICAL EXPLOSION OCCURRED. THE ELECTRICIAN HAD APPARENTLY CAUSED A GROUND FAULT. HE RECEIVED FIRST AND SECOND DEGREE BURNS TO HIS FACE AND LEFT ARM. HE WAS HOSPITALIZED FOR HIS INJURIES.
Keywords: burn, clothing, electric arc, e gi iii, electrical, electrician, electrical work, lockout, electrical box, electrical fault
Employee # Inspection Age Sex Degree Nature Occupation
1 105477426 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close