Accident: 200150225 - Burn - Electrical Fault In Test Equipmennt

Accident: 200150225 -- Report ID: 0214700 -- Event Date: 03/14/1999
InspectionOpen DateSICEstablishment Name
30014073803/15/19994911Keyspan Energy Corp.
An employee with 22 years of experience was installing a ground and test device into a saltwater-circulating-pump switchgear cubical. The device was used to ground and megger a circuit under repair. Apparently, the employee did not follow the procedures for installing the device and hung the device's grounding cables on its upper terminals before installing the device into the cubical. The upper terminals became energized when the device was installed. This caused a three-phase electrical fault. The ensuing electric arc burned the employee. He was hospitalized with second- and third-degree burns over 90 percent of his body and with inhalation injuries. The employee died of his injuries 10 days after the accident.
Keywords: burn, electric arc, lung, electrical, electrical work, test equipment, e ptd, elec utility work, electrical fault
Employee # Inspection Age Sex Degree Nature Occupation
1 300140738 Fatality Burn/Scald(Heat) Not specified mechanics and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close