Accident Report Detail
Accident: 200051696 - Seven Employees Burned In Fire At Cold Storage Facility
Accident: 200051696 -- Report ID: 0728900 -- Event Date: 06/21/2002 | |||||||
Inspection | Open Date | SIC | Establishment Name | ||||
---|---|---|---|---|---|---|---|
303731988 | 06/25/2002 | 1711 | Prime Refrigeration | ||||
Inspection | Open Date | SIC | Establishment Name | ||||
303731962 | 06/24/2002 | 4222 | United States Cold Storage, Inc. | ||||
Inspection | Open Date | SIC | Establishment Name | ||||
303731988 | 06/25/2002 | 1711 | Prime Refrigeration | ||||
Inspection | Open Date | SIC | Establishment Name | ||||
303731962 | 06/24/2002 | 4222 | United States Cold Storage, Inc. | ||||
Inspection | Open Date | SIC | Establishment Name | ||||
303731988 | 06/25/2002 | 1711 | Prime Refrigeration | ||||
On June 21, 2002, Employees #1 through #5 with Prime Refrigeration, and Employees #6 and #7 with United States Cold Storage, were burned in a flash fire/explosion at a cold storage facility in Omaha, NE. One of the Prime Refrigeration employees was using an oxy/acetylene torch to cut into an ammonia cooling system vessel that had been evacuated of ammonia and drained of lubricating oil. The vessel had evidently not been thoroughly cleaned or purged, allowing residual oil to fuel the fire. Employees #1 and #2 were hospitalized, and the others were treated and released. | |||||||
Keywords:
ammonia, cleaning, purging, burn, fire, lubricating fluid
| |||||||
End Use | Proj Type | Proj Cost | Stories | NonBldgHt | Fatality | ||
Other building | Alteration or rehabilitation | Under $50,000 | 1 | ||||
Employee # | Inspection | Age | Sex | Degree | Nature | Occupation | Construction |
1 | 303731988 | Hospitalized injury | Burn/Scald(Heat) | Welders and cutters | FallDist: FallHt: Cause: Installing equipment (HVAC and other) FatCause: Fire/explosion |
||
2 | 303731962 | Non Hospitalized injury | Burn/Scald(Heat) | Operating engineers | FallDist: FallHt: Cause: FatCause: |
||
3 | 303731988 | Hospitalized injury | Burn/Scald(Heat) | Welders and cutters | FallDist: FallHt: Cause: Installing equipment (HVAC and other) FatCause: Fire/explosion |
||
4 | 303731988 | Non Hospitalized injury | Burn/Scald(Heat) | Plumbers, pipefitters and steamfitters | FallDist: FallHt: Cause: Installing equipment (HVAC and other) FatCause: Fire/explosion |
||
5 | 303731962 | Non Hospitalized injury | Burn/Scald(Heat) | Industrial engineers | FallDist: FallHt: Cause: FatCause: |
||
6 | 303731988 | Non Hospitalized injury | Burn/Scald(Heat) | Welders and cutters | FallDist: FallHt: Cause: Installing equipment (HVAC and other) FatCause: Fire/explosion |
||
7 | 303731988 | Non Hospitalized injury | Burn/Scald(Heat) | Welders and cutters | FallDist: FallHt: Cause: Installing equipment (HVAC and other) FatCause: Fire/explosion |