Accident: 170586176 - Burn - Electrical Fault In Circuit Breaker

Accident: 170586176 -- Report ID: 0950635 -- Event Date: 10/05/1993
InspectionOpen DateSICEstablishment Name
11212802010/06/19931629Fluor Daniel Inc
An electrical engineer was inside the cubicle of a 12-kilovolt circuit breaker, surveying the breaker's components. No lockout procedure had been followed, and the input terminals were not guarded. An electrical fault developed between exposed phases of the supply side of the circuit breaker, and the ensuing electric arc burned the engineer. The employee was hospitalized with second- and third-degree burns to his face, body, and hands.
Keywords: burn, clothing, electric arc, electrical, lockout, e ptd, circuit breaker, elec utility work, electrical fault, switchgear
Employee # Inspection Age Sex Degree Nature Occupation
1 112128020 Hospitalized injury Electric Shock Electrical and electronic engineers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.