Accident: 170375927 - Employees Exposed To Chlorine Gas

Accident: 170375927 -- Report ID: 0950614 -- Event Date: 03/21/1995
InspectionOpen DateSICEstablishment Name
11970647104/03/19954952Ebmud East Bay Municipal Utilities District
On March 21, 1995, Employees #1 and #2, of EBMUD, were exposed to high levels of chlorine gas during a routine maintenance operation on a valve in the chlorination piping system. The scheduled work was to have been performed on CPRV #1 on evaporator #1 in the evaporator room. The line to be opened had been evacuated of chlorine and all incoming chlorine ability had been locked out and tagged out. Both employees had been trained on the procedure and had reviewed the procedure with their supervisor. Both employees were equipped with supplied-air full face mask respirators. Instead of opening CPRV #1, they opened CPRV #2, which was under 90 lb of chlorine gas pressure. Employee #1 was hit directly in the face mask with chlorine gas, and some entered the mask. Employee #2 was unaffected. Alarms sounded and the release was stopped from outside the room. Employee #1 was seen at a hospital and released with no permanent injury.
Keywords: maintenance, open valve, work rules, inhalation, gas, chlorine, high pressure, accidental discharge, inattention
Employee # Inspection Age Sex Degree Nature Occupation
1 119706471 Non Hospitalized injury Other Occupation not reported
2 119706471 Non Hospitalized injury Other Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close