Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 170174726 - Asphalt Tank Explodes When Vapors Ignited By Heating Coils

Accident: 170174726 -- Report ID: 0950614 -- Event Date: 11/08/1990
InspectionOpen DateSICEstablishment Name
11182404111/08/19902951Western Colloid
Employee #1 turned on the burner to a 25,000 gallon asphalt tank in an attempt to release a stuck level indicator float. The approximately 600 gallons of asphalt that remained in the tank was not enough to cover the heating coils. As the temperature of the coils reached an estimated 1,000 to 1,200 degrees F, the vapors released from the asphalt ignited. The resulting explosion threw the top of the tank 200 feet, and it crashed through a roof of a company warehouse. No injuries were reported.
Keywords: maintenance, vapor, flammable vapors, work rules, storage tank, jammed, explosion, hot asphalt, flying object, high temperature
Employee # Inspection Age Sex Degree Nature
1 111824041

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.