Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 14570246 - Electric Shock - Direct Contact With Energized Parts

Accident: 14570246 -- Report ID: 0522500 -- Event Date: 11/01/1986
InspectionOpen DateSICEstablishment Name
10007598511/03/19865039Owens-Corning Fiberglass Corporation
InspectionOpen DateSICEstablishment Name
10007599311/03/19867361Quality Personnel, Inc.
TWO EMPLOYEES WERE REMOVING A TAKE-UP REEL OF INSULATION FROM THE END OF A SLITTING MACHINE. THE SPINDLE IN THE MIDDLE OF THE ROLL WAS ABOUT 6 FEET LONG. A 10-INCH-BY-7-INCH PANELBOARD WAS MOUNTED ON THE SIDE OF THE SLITTING MACHINE AT A HEIGHT OF 19.5 INCHES FROM THE FLOOR. THE COVER FOR THE PANELBOARD HAD BEEN REMOVED BECAUSE THE CIRCUIT BREAKER INSIDE HAD TO BE RESET REPEATEDLY. (THE BREAKER COULD BE RESET WITH THE COVER IN PLACE, BUT THE EMPLOYEES DID NOT REALIZE THAT.) THE LEG OF ONE OF THE EMPLOYEES CONTACTED CIRCUIT PARTS EXPOSED AS A RESULT OF THE MISSING COVER AND ENERGIZED AT 240 VOLTS. THE EMPLOYEE, WHO WAS IN CONTACT WITH THE GROUNDED MACHINE, WAS ELECTROCUTED.
Keywords: electrical, e gi v, electrocuted, panelboard, unguarded live parts, circuit breaker
Employee # Inspection Age Sex Degree Nature Occupation
1 100075985 Fatality Electric Shock Production helpers
2 100075993 Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close