Accident: 14523880 - Employees Overcome By Blast Furnace Gas

Accident: 14523880 -- Report ID: 0522500 -- Event Date: 04/03/1984
InspectionOpen DateSICEstablishment Name
165949904/06/19843443Monroe Incorporated
InspectionOpen DateSICEstablishment Name
165948104/12/19841741Chiz Bros Inc
InspectionOpen DateSICEstablishment Name
165949904/06/19843443Monroe Incorporated
InspectionOpen DateSICEstablishment Name
165947304/04/19843312Wheeling Pittsburg Steel Corporation North Facili
InspectionOpen DateSICEstablishment Name
165949904/06/19843443Monroe Incorporated
A CONTRACTOR AND SUBCONTRACTOR WORKING IN THE NUMBER ONE BOILER HOUSE WERE AT THE WEST END OF THE BUILDING. THE WATER IN THE DRIP LEG RESERVOIR FOR THE FIVE FOOT BLAST FURNACE MAIN BECAME LOW. THE WATER LEVEL FELL TO WITHIN 34 INCHES OF THE BOTTOM OF THE DRIP LEG. SINCE THE GAS PRESSURE WITHIN THE MAIN IS AT 34 INCHES OF WATER, THE GAS BEGAN TO BLOW OUT THE 14 INCH DRIP LEG FROM THE FIVE FOOT DIAMETER GAS MAIN. THE DRIP LEG IS LOCATED AT THE NORTHWEST CORNER OF THE NUMBER ONE BOILER HOUSE. THE WATER LINE TO THE RESERVOIR WAS EITHER TURNED OFF OR THE VALVE WAS PLUGGED. EMPLOYEES AT ALL LEVELS OF THE WESTERN 1/3 OF THE BOILER HOUSE WERE EXPOSED TO EXCESSIVE LEVELS OF CARBON MONOXIDE. MANY PASSED OUT. MANY RESCUERS UNEQUIPPED WITH RESPIRATORS PASSED OUT ALSO. ALL AFFECTED EMOLOYEES WERE HOSPITALIZED. THE EMPLOYEES WERE NOT TRAINED IN THE USE OF RESPIRATORS OR IN GAS RESCUE PROCEDURES.
Keywords: unconsciousness, ppe, inhalation, carbon monoxide, respirator, blast furnace, gas leak
Employee # Inspection Age Sex Degree Nature Occupation
1 1659499 Hospitalized injury Asphyxia Occupation not reported
2 1659481 Occupation Not Listed
3 1659499 Hospitalized injury Asphyxia Occupation not reported
4 1659473 Occupation Not Listed
5 1659499 Hospitalized injury Asphyxia Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.