Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 14497010 - Electric Shock - Ground Fault In Battery Charger

Accident: 14497010 -- Report ID: 0627100 -- Event Date: 08/23/1988
InspectionOpen DateSICEstablishment Name
10678150308/24/19883612Magnetek Universal Manufacturing
Two employees were working out of a rubber-tired, battery-powered, hydraulic scissor lift. They were using an extension cord set to charge the batteries, and the cord became disconnected from the wall receptacle to which it had been connected. One of the employees climbed down from the lift and plugged the cord back into the receptacle. As he climbed back onto the platform, he grabbed an overhead support bar that was suspended from the ceiling. He received an electric shock and froze to the support rod. He was electrocuted. Investigation revealed that a rubber grommet was missing from a hole in the battery charger where the charger's 305-millimeter-long power supply cord exited. The neutral conductor on the cord had a frayed and bare spot about 13 millimeters long and had burn marks on it. The upper part of the hole in the charger also had a burn mark. The power supply cord contained no equipment grounding conductor. The extension cord was wired properly but the wall receptacle had reversed polarity. This ground fault had energized the scissor lift and electrocuted the employee.
Keywords: e gi v, electrical, battery charger, cord set, electrocuted, ground fault, equipment grounding
Employee # Inspection Age Sex Degree Nature Occupation
1 106781503 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close