Accident: 14467146 - Electric Shock - Contact With Energized Motor Frame

Accident: 14467146 -- Report ID: 0626000 -- Event Date: 08/04/1984
InspectionOpen DateSICEstablishment Name
140490408/07/19841389Operators Incorporated Subsidiary Of Tenneco Oil C
AN EMPLOYEE WAS WORKING NEAR AN ELECTRIC-MOTOR-DRIVEN CENTRIFUGAL PUMP. THE MOTOR WAS SUPPLIED BY A THREE-PHASE, UNGROUNDED DELTA CIRCUIT. ONE PHASE OF A SET OF TRANSMISSION LINES WAS IN CONTACT WITH A BRACKET ON A UTLITY POLE. THE BRACKET WAS IN ELECTRICAL CONTACT WITH THE GROUND WIRE RUNNING THE ENTIRE LENGTH OF THE POLE. THE GROUNDING CONDUCTORS FROM BOTH THE CONTROL PANEL AND THE ELECTRIC MOTOR WERE BONDED TO THE GROUND WIRE, THEREBY ENERGIZING THE FRAME OF THE ELECTRIC MOTOR AND THE PUMP. THE FRAME SUPPORTING THE ELECTRIC MOTOR AND PUMP RESTED ON A 1-INCH-BY-40-INCH RUBBER STRIP USED TO ABSORB MOTOR VIBRATIONS. THIS ALSO ISOLATED THE METAL PARTS FROM GROUND POTENTIAL AT THE MOTOR SITE. WHEN THE EMPLOYEE INVESTIGATED THE ARCING OCCURRING FROM THE FRAME TO THE CONCRETE SLAB, HE CAME IN CONTACT WITH THE ENERGIZED PARTS AND WAS ELECTROCUTED.
Keywords: electric motor, e gi iii, electrical, potential gradient, electrocuted, ground fault, equipment grounding, system grounding
Employee # Inspection Age Sex Degree Nature Occupation
1 1404904 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close