Accident: 14379457 - Electric Shock - Direct Contact With Energized Parts

Accident: 14379457 -- Report ID: 0524500 -- Event Date: 05/30/1986
InspectionOpen DateSICEstablishment Name
10176294606/03/19864911Central Illinois Public Service
AN EMPLOYEE WAS WORKING FROM AN AERIAL LIFT, GROUNDING THE LINE SIDE OF AN OIL CIRCUIT BREAKER. HE POSITIONED THE BUCKET BETWEEN THE SOUTH PHASE AND THE CENTER PHASE AND HAD ATTACHED ONE END OF THE PROTECTIVE GROUND TO THE STEEL STRUCTURE SERVING AS GROUND. THE GROUNDING CABLE PASSED BETWEEN THE INSULATOR AND THE BLADE OF A SWITCH. THIS POSITION WOULD HAVE INTERFERED WITH THE REMOVAL OF THE SWITCH. THERE WERE NO WITNESSES TO THE ACCIDENT, BUT IT WAS APPARENT THAT THE EMPLOYEE TRIED TO PASS THE LOOSE END OF THE GROUNDING CABLE AROUND THE BLADE OF THE SWITCH. IN SO DOING, HE APPARENTLY CONTACTED THE ENERGIZED BLADE OF THE SWITCH AND WAS ELECTROCUTED.
Keywords: elec protect equip, protective grounding, electrical, electric switch, power line worker, electrocuted, e ptd, circuit breaker, elec utility work
Employee # Inspection Age Sex Degree Nature Occupation
1 101762946 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close