Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Accident Report Detail

Accident: 14216360 - Seven Employees Suffer Overexposure To Chlorine Gas

Accident: 14216360 -- Report ID: 0150900 -- Event Date: 05/31/1994
InspectionOpen DateSICEstablishment Name
10380778005/31/19944952Town Of Enfield Water Pollution Control Plant
At 7:45 a.m. on May 31, 1994, a tanker truck delivered sodium hypochlorite to a plant. Approximately 20 gallons were placed in a tank containing 200 gallons of ferric chloride. A reaction occurred that released chlorine gas outside the plant's main building. Employees #1 through #7 experienced short-term overexposure. All were sent to Johnson Memorial Hospital. Employees #1 and #2 were kept 48 hours for observation. The driver had been told three times that the connection was ferric chloride. The hypochlorite fill was 1,000 ft away from the ferric chloride fill. The plant did not verify that the truck was delivering sodium hypochlorite; a ferric chloride delivery was expected the same day. The plant had been using sodium hypochlorite for approximately one month. There were no written procedures for deliveries. Violations of 1910-120, 134, 1200 were found.
Keywords: respiratory, sodium hypochlorite, work rules, chlorine, chemical reaction, overexposure, tank, inattention
Employee # Inspection Age Sex Degree Nature Occupation
1 103807780 Non Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators
2 103807780 Non Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators
3 103807780 Non Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators
4 103807780 Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators
5 103807780 Non Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators
6 103807780 Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators
7 103807780 Non Hospitalized injury Poisoning(Systemic) Water and sewage treatment plant operators

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close