Accident: 115993.015 - Employee Is Killed By Electrocution

Accident: 115993.015 -- Report ID: 0627510 -- Event Date: 05/04/2019
InspectionOpen DateSICEstablishment Name
1398621.01505/06/2019Ogt, Llc
At 11:00 a.m. on May 4, 2019, an employee was working by himself and using an el ectrical knife to clean and strip lines in a breaker box. The employee was kille d when he accidentally came in contact with an energized part and was electrocut ed. Normally these energized parts would have an arc flash shield in front of th em but when the employee was found the shield had been removed. A horizontal cut mark was found on the outer sheath of the electrical box where the employer bel ieved the employee had been cutting. The cutting motion would have put the emplo yee's arm directly in front of the where the energized parts were. There were no signs of electrical gloves. Despite the breaker being locked in the off positio n, the entire unit was not deenergized.
Keywords: electric cable, electrician, electrocuted, ppe
End Use Proj Type Proj Cost Stories NonBldgHt Fatality
Other building New project or new addition   0 0 X
Employee # Inspection Age Sex Degree Nature Occupation Construction
1 1398621.015 55 M Fatality Electrical and electronic technicians FallDist:
FallHt:
Cause: Installing equipment (HVAC and other)
FatCause:

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.