Accident: 112330.015 - Crane Load Is Dropped Through Roof With No Injuries Sustaine

Accident: 112330.015 -- Report ID: 0523300 -- Event Date: 10/31/2018
InspectionOpen DateSICEstablishment Name
1357378.01510/31/2018Aecom, Inc.
InspectionOpen DateSICEstablishment Name
1357384.01510/31/2018J.P. Cullen & Sons, Inc.
InspectionOpen DateSICEstablishment Name
1357387.01510/31/2018Innova Global Inc.
InspectionOpen DateSICEstablishment Name
1357380.01510/31/2018Alliant Energy Corporation
At approximately 8:40 a.m. on or about October 31, 2018, a Manitowoc Lattice Boom Crane (Model 4100, 230 ton) was hoisting ten sheets of metal siding with two Rockford 16 nylon straps in a basket configuration (basket max load: 12,800 pounds). The sheets were approximately 24 feet long, 3 feet wide, and weighed approximately 100 pounds each for a total load of 1,000 pounds. As the crane was swinging over a section of a building, the edge of the metal siding material cut through the nylon straps, thus resulting in the load falling in a vertical position approximately 20 feet through the building roof causing property damage to the roof and finishes within the building. The areas within the swing radius were barricaded and cleared prior to lifting/hoisting the materials. No sling protection to prevent exposure to sharp edges was utilized prior to the incident occurring. The crane operator and rigger were certified. There was significant property damage but no injuries were sustained.
Keywords: basket, crane operator, falling object, metal siding, crane load
End Use Proj Type Proj Cost Stories NonBldgHt Fatality
Powerplant New project or new addition  
Employee # Inspection Age Sex Degree Nature Construction
1 1357378.015 FallDist:
FallHt:
Cause:
FatCause: Struck by falling object/projectile
2 1357384.015 FallDist:
FallHt:
Cause:
FatCause: Struck by falling object/projectile
3 1357387.015 FallDist:
FallHt:
Cause:
FatCause: Struck by falling object/projectile
4 1357380.015 FallDist:
FallHt:
Cause:
FatCause: Struck by falling object/projectile

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.