Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
This violation item has been deleted.
Inspection Nr: 987108.015
Citation: 01005
Citation Type: Serious
Abatement Date: 03/11/2015
Initial Penalty: $7,000.00
Current Penalty: $0.00
Issuance Date: 01/26/2015
Nr Instances: 6
Nr Exposed: 20
Related Event Code (REC): A
Gravity: 10
Report ID: 0729700
Contest Date: 02/18/2015
Final Order: 08/10/2015
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 08/10/2015 | $0.00 | 03/11/2015 | Serious | |
| Penalty | C: Contested | 02/18/2015 | $7,000.00 | 03/11/2015 | Serious | |
| Penalty | Z: Issued | 01/26/2015 | $7,000.00 | 03/11/2015 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: On or about July 29th, 2014 employees working in the Isomerization Unit were exposed to fire and explosion hazards. The employer had installed electrical motors that were not rated for Class 1 Division 2 locations. The following motors were not rated for Class 1 Division 2 hazardous locations: a) North Separator Condensate Pump Motor , ID# N01L3100131R-1, for pump P2217. b) South Separator Condensate Pump Motor , ID# N01L3100131R-2, for pump P2216. c) Light Isomerate Pump Motor, SN# B581622-010001, for pump P2193. d) Light Isomerate Pump Motor, SN# 9603, for pump P3726. e) Isom East Stabilizer Reflux Pump Motor, SN#FHFT160S008, for pump P0746. f) Isom West Stabilizer Reflux Pump Motor, SN# AHFT0273020, for pump P0745
Translate