Violation Detail
Standard Cited: 19100335 A02 I Safeguards for personnel protection.
Inspection Nr: 980882.015
Citation: 01004
Citation Type: Serious
Abatement Date: 01/02/2015 2
Initial Penalty: $4,900.00
Current Penalty: $4,900.00
Issuance Date: 12/10/2014
Nr Instances: 2
Nr Exposed: 1
Related Event Code (REC): A
Gravity: 10
Report ID: 0936200
Contest Date:
Final Order: 01/05/2015
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 12/10/2014 | $4,900.00 | 01/02/2015 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools for handling equipment when the tools or handling equipment might have made contact with such conductors or parts: On or about 13 June 2014 At Naval Base Ventura, Point Mugu, an employee working on T211 a 150KVA 4160-120/208V 3 Phase delta/wye dry pack transformer reached in through the high voltage side with a Ryobi 18 V Impact Wrench - Model P260 non-insulated drill and socket to secure the neutral line bolt that was within 12 inches from a live circuit exposing the employee to an electrical hazard that resulted in an electrocution.