Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 97716.015
Citation: 01002
Citation Type: Serious
Abatement Date: 01/26/2012 2
Initial Penalty: $4,500.00
Current Penalty: $2,700.00
Issuance Date: 12/27/2011
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): A
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 01/18/2012
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/18/2012 | $2,700.00 | 01/26/2012 | Serious | |
| Penalty | Z: Issued | 12/27/2011 | $4,500.00 | 01/26/2012 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: As a substitute for the fixed wiring of a structure; a) At the Yenkin-Majestic Paint Corporation, the battery charging station in the warehouse had a Hobart battery charger (Model # 865c3-18, Serial # 389cs09135), that was sitting on a pallet on the floor. The manufacturer of the battery charger required it to be securely mounted to concrete floor or a base. The battery charger was powered using approximately 10 foot flexible cord (type SEOOW) instead of fixed wiring in conduit.
Translate