Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 966254.015
Citation: 01004
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $2,550.00
Current Penalty: $1,785.00
Issuance Date: 05/30/2014
Nr Instances: 3
Nr Exposed: 3
Related Event Code (REC):
Gravity: 1
Report ID: 0215800
Contest Date:
Final Order: 06/24/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/24/2014 | $1,785.00 | Serious | ||
Penalty | Z: Issued | 05/30/2014 | $2,550.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Electrical Maintenance Room for Department 53, on or about 4/8/14: : Employees using duplex metal outlet box connected to a flexible cord that was not in accordance with UL approval. Box is listed for permanent mounting only. b) Tumbler Area, on or about 4/8/14: : Employees using duplex metal outlet box connected to a flexible cord that was not in accordance with UL approval. Box is listed for permanent mounting only. c) Bechlar Area, on or about 4/8/14: : Employees using a quad metal outlet box and a duplex metal outlet box connected to flexible cords that were not in accordance with UL approval. Boxes are listed for permanent mounting only.