Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 928186.015
Citation: 02004
Citation Type: Other
Abatement Date: 03/04/2014 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/05/2014
Nr Instances: 3
Nr Exposed: 5
Related Event Code (REC):
Gravity:
Report ID: 0418400
Contest Date:
Final Order: 03/04/2014
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/04/2014 | $0.00 | 03/04/2014 | Other | |
| Penalty | Z: Issued | 02/05/2014 | $0.00 | 03/04/2014 | Other |
Text For Citation: 02 Item/Group: 004 Hazard:
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a) On August 8, 2013, and times prior thereto, at the sawmill in Whigham, GA, the employer allowed live parts exceeding 50V at the main saw carriage-drive junction box to be without an approved cover, exposing employees to hazards not limited to electric shock following accidental contact. b) On August 8, 2013, and times prior thereto, at the sawmill in Whigham, GA, the employer allowed live parts exceeding 50V at the large edger under feed pulley to be without an approved cover, exposing employees to hazards not limited to electric shock following accidental contact. c) On August 8, 2013, and times prior thereto, at the sawmill in Whigham, GA, the employer allowed live parts exceeding 50V at the trimmer top discharge belt motor without an approved cover, exposing employees to hazards not limited to electric shock following accidental contact. ABATEMENT CERTIFICATION IS REQUIRED FOR THE THIRD INSTANCE ONLY.
Translate