Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 783282.015
Citation: 01002
Citation Type: Serious
Abatement Date: 03/01/2015 2
Initial Penalty: $5,500.00
Current Penalty: $4,125.00
Issuance Date: 06/06/2013
Nr Instances: 6
Nr Exposed: 22
Related Event Code (REC):
Gravity: 5
Report ID: 0522500
Contest Date: 06/27/2013
Final Order: 01/13/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 03/11/2014 | $1,375.00 | 07/11/2013 | Serious | |
Penalty | F: Formal Settlement | 01/13/2014 | $4,125.00 | 03/01/2015 | Serious | |
Penalty | Z: Issued | 06/06/2013 | $5,500.00 | 07/11/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process shall include: Piping and instrument diagrams (P&ID's): a. The P&ID (Drawing #00070PID) Red Diamond Emulsion Process Flow Oil Based Products, dated on or about March 8, 2001, did not include a P&ID legend and was not accurate in that it identified the wax module/operation which was removed from the process on or about the end of 2011 and/or beginning of 2012. b. The P&ID (Drawing #00070PID) Red Diamond Emulsion Process Flow Oil Based Products, dated on or about March 8, 2001, was not accurate in that it identified the gassing process/operation which was removed from the process around 2004 or after. c. The P&ID (Drawing #00070PID) Red Diamond Emulsion Process Flow Oil Based Products, dated on or about March 8, 2001, was not accurate in that the product recycle tank T-OIL05, valve at the bottom of the recycle tank, Wilden pump P-129 (Model M-8), and piping were not identified. d. The P&ID (Drawing #00070PID) Red Diamond Emulsion Process Flow Oil Based Products, dated on or about March 8, 2001, was not accurate in that the premix tank was not identified with its name. e. The P&ID (Drawing #EMULSIONPROCESSFLOW) Red Diamond Emulsion Process Flow Diagram, revised on or about January 5, 2005, did not include a P&ID legend and was not accurate in that it identified the wax module/operation which was removed from the process on or about the end of 2011 and/or beginning of 2012. f. The P&ID (Drawing #EMULSIONPROCESSFLOW) Red Diamond Emulsion Process Flow Diagram, revised on or about January 5, 2005, was not accurate in that it identified the gassing process/operation which was removed from the process around 2004 or after.