Violation Detail
Standard Cited: 19100305 J02 V Wiring methods, components, and equipment for general use.
Inspection Nr: 439251.015
Citation: 01006
Citation Type: Serious
Abatement Date: 11/23/2012 2
Initial Penalty: $3,600.00
Current Penalty: $3,600.00
Issuance Date: 11/20/2012
Nr Instances:
Nr Exposed: 40
Related Event Code (REC):
Gravity: 5
Report ID: 0419400
Contest Date:
Final Order: 12/05/2012
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 12/05/2012 | $3,600.00 | 11/23/2012 | Serious | |
| Penalty | Z: Issued | 11/20/2012 | $3,600.00 | 11/23/2012 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is covered (attachment plug cap not inserted and receptacle covers closed). Note to paragraph (j)(2)(v) of this section. A receptacle is considered to be in a location protected from the weather when it is located under roofed open porches, canopies, marquees, or the like and where it will not be subjected to a beating rain or water runoff. Mississippi Phosphate Corporation located in Pascagoula, MS was cited for the same violation related to inspection number 311419295, citation was issued on May 12, 2009. (a) On or about June 14, 22012 electrical receptacles installed outdoors in the Sulfuric Acid plant number 3 did not have enclosures to become weather proof for a wet environment. Mississippi Phosphate Corporation was cited in March 2009 for these same violations in the Sulfuric Acid Plant. (b) On or about June 14, 2012 a electrical box for lighting was not covered to become weather proof in a wet environment.
Translate