Violation Detail
Standard Cited: 19100119 M01 Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 314769704
Citation: 01016
Citation Type: Serious
Abatement Date: 09/29/2011
Initial Penalty: $7,000.00
Current Penalty:
Issuance Date: 09/12/2011
Nr Instances: 1
Nr Exposed: 12
Related Event Code (REC):
Gravity: 10
Report ID: 0625700
Contest Date: 09/23/2011
Final Order: 07/19/2012
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 07/19/2012 | 09/29/2011 | Serious | ||
Penalty | Z: Issued | 09/12/2011 | $7,000.00 | 09/29/2011 | Serious |
Text For Citation: 01 Item/Group: 016 Hazard: REFINERY
29 CFR 1910.119(m)(1): The employer did not investigate each incident which resulted in, or could reasonably have resulted in a catastrophic release of highly hazardous chemicals in the workplace: The employer failed to investigate an incident in the hydrocracker unit which occurred when one of three check valves on the discharge of pump P-103 failed to close, causing the overpressure of well water tank TK-1 such that its hinged lid blew off, and resulting in the release of H2S that had backed into tank TK-1 from D-103, the high pressure separator, which contains hydrocarbons, H2, H2S, and NH3. This violation was documented on or about June 27, 2011. Pursuant to 29 CFR 1903.19(d), within 10 days, the employer must submit an abatement plan describing the actions it is taking to ensure that all incidents and near misses are investigated. The violation must be abated no later than 10 days from the receipt of this citation.