Text For Citation: 01 Item/Group: 001 Hazard: EXPLOSION
SCRR 71-112A: Failed to furnish a place of employment which is free of recognized hazards which may cause death or serious physical harm to his employees and comply with this regulation and other occupational safety and health rules and regulations promulgated under Chapter 15 of Title 41, Code of Laws, State of South Carolina, 1976, as amended, as follows: A. Employer knew or should have known that three maintenance mechanics while removing a blind flange cover on the DR-501 reactor that utilized hydrogen in the Purified Terephthalic Acid unit of Plant Two were exposed to the hazards of fire and explosion form a hazardous atmosphere. A feasible and useful method to correct the hazard, among others is to: 1) Install and maintain a hydrogen detector to alert employees of the presence of hydrogen inside the reactor prior to line/flange breaking. 2) A vent system on all nozzles, man ways or other high points on the DR-501 reactor and visually verify the overflowing of water from all vents.