Violation Detail
Standard Cited: 19100107 E04 Spray finishing using flammable and combustible materials.
Inspection Nr: 303249742
Citation: 01001
Citation Type: Serious
Abatement Date: 06/20/2000 X
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 06/16/2000
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): A
Gravity:
Report ID: 0355123
Contest Date: 06/22/2000
Final Order: 11/17/2000
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Y: State Decision | 11/17/2000 | $7,000.00 | 06/20/2000 | Serious | |
| Penalty | Z: Issued | 06/16/2000 | $7,000.00 | 06/20/2000 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard: CHEMICAL
40.1-51.1.(a)-Code of Virginia: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that: Spray Booth - The pump that was used to supply flammable paint to the spray application process was not provided with a means to automatically shut off the supply of paint liquid in case of a fire or operation of the extinguishing system as noted during an inspection on 12/20/00. "One feasible means of abatement is to install a device that would comply with the requirements of NATIONAL FIRE PROTECTION ASSOCIATION PUBLICATION NFPA 33 Standard for Spray Application Using Flammable or Combustible Materials 1995 Section 6-4.5 and NATIONAL FIRE PROTECTION ASSOCIATION PUBLICATION NFPA 17 Dry Chemical Extinguishing Systems Section 3-5.2."