Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1730312.015
Citation: 01002B
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/13/2024
Nr Instances: 1
Nr Exposed: 36
Related Event Code (REC):
Gravity: 1
Report ID: 0216000
Contest Date:
Final Order: 08/30/2024
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/30/2024 | $0.00 | Serious | ||
| Penalty | Z: Issued | 08/13/2024 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 002B Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening whwere they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Location: beside exit door area On or about: 2/20/24 a) The electrical breaker box was blocked by stored materials. NOTE: Because abatement of this violation is already documented in the inspection casefile, the employer need not submit certification or documentation of abatement for this violation as normally required by 29 CFR 1903.19.