Violation Detail
Standard Cited: 19100037 A04 Maintenance, safeguards, and operational features for exit routes.
Inspection Nr: 1664899.015
Citation: 03003
Citation Type: Other
Abatement Date: 07/05/2023 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/07/2023
Nr Instances: 1
Nr Exposed: 40
Related Event Code (REC):
Gravity:
Report ID: 0936200
Contest Date:
Final Order: 06/28/2023
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/28/2023 | $0.00 | 07/05/2023 | Other | |
Penalty | Z: Issued | 06/07/2023 | $0.00 | 07/05/2023 | Other |
Text For Citation: 03 Item/Group: 003 Hazard:
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times. Cashier Cage: On and/or before April 19, 2023, employee(s) conducted clerical, customer service, and cash counting. Multiple ceiling tiles throughout the cash cage had holes and/or were improperly installed. This condition would delay the activation of the sprinkler system(s) preventing a proper barrier and restricting the movement of smoke in accordance with NFPA 101 8.5.1. Employee(s) were exposed to fire and smoke hazard(s).