Violation Detail
Standard Cited: 19100303 G01 I C General.
Inspection Nr: 1598429.015
Citation: 01004
Citation Type: Other
Abatement Date: 11/29/2022 2
Initial Penalty: $2,486.00
Current Penalty: $0.00
Issuance Date: 11/01/2022
Nr Instances: 1
Nr Exposed: 8
Related Event Code (REC):
Gravity: 1
Report ID: 0830500
Contest Date:
Final Order: 11/22/2022
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/22/2022 | $0.00 | 11/29/2022 | Other | |
| Penalty | Z: Issued | 11/01/2022 | $2,486.00 | 11/29/2022 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303: a) Baker Industrial Fabrication, LLC, 5660 Iris Pkwy, Frederick, CO 80504: On or about 5/24/2022, the employer did not ensure that the space about the electrical cabinet on the south-east side of the shop was not clear of obstruction to the floor. There were multiple welding leads laying on the floor, just in front of and below the electrical cabinet. This exposed workers to electrical and fire hazards.
Translate