Violation Detail
Standard Cited: 19100303 G01 I General.
Inspection Nr: 1543109.015
Citation: 01005
Citation Type: Serious
Abatement Date: 02/02/2022 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/06/2022
Nr Instances: 5
Nr Exposed: 27
Related Event Code (REC):
Gravity: 1
Report ID: 1032100
Contest Date:
Final Order: 02/23/2022
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/06/2022 | $0.00 | 02/02/2022 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: a) Machine Area/Green Desk - On or about July 20, 2021, the H-12 three phase panel had items placed in the working space to include a green desk and chair, exposing employees to fire and electrical hazards. b) Maintenance Area - On or about July 20, 2021, the I-4 three phase panel had items stored within the 30 inches to include lamp, paper, and cords, exposing employees to fire and electrical hazards. c) Grinding Area - On or about July 20, 2021, a 208 Volt electrical panels (J-2) had combustible items and a compressed gas cylinder stored directly in the working space, exposing employees to fire and electrical hazards. d) Machine Shop - On or about July 20, 2021, a 208 Volt electrical panel (A) had combustible items items stored directly in the working space, exposing employees to fire and electrical hazards. e) Breakroom - On or about July 20, 2021, a 208 Volt, panel (V) had combustible items stored directly in front of the working space, exposing employees to fire and electrical hazards.
Translate