Violation Detail
Standard Cited: 19100269 L03 III Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1513721.015
Citation: 01001
Citation Type: Other
Abatement Date: 07/01/2021 2
Initial Penalty: $13,653.00
Current Penalty: $13,653.00
Issuance Date: 06/07/2021
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): R
Gravity: 10
Report ID: 0729700
Contest Date:
Final Order: 07/07/2021
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/07/2021 | $13,653.00 | 07/01/2021 | Other | |
| Penalty | Z: Issued | 06/07/2021 | $13,653.00 | 07/01/2021 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approached or took any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed: On or about February 02, 2021 - Employees engaged in activities of applying the grounds to the pole with a shotgun were exposed to electrical burn hazards in that employer failed to ensure the employees would not approach too close and contact the exposed energized parts. The Minimum Approach Distances were not maintained, employees were within 3 feet of the de-energized line with induced voltage. 29 CFR 1903.19(d)(1) requires certification and documentation that the abatement of the above violation is complete.
Translate