Violation Detail
Standard Cited: 19260960 G05 IV
This violation item has been deleted.
Inspection Nr: 1506046.015
Citation: 01001
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $10,533.00
Current Penalty: $0.00
Issuance Date: 03/31/2021
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0419700
Contest Date:
Final Order: 05/03/2021
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/03/2021 | $0.00 | Serious | ||
| Penalty | Z: Issued | 03/31/2021 | $10,533.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.960(g)(5)(iv): The protection for the employee''s head may consist of head protection meeting � 1926.100(b)(2) and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated incident energy exposure is less than 13 cal/cm2 for exposures involving single-phase arcs in open air or 9 cal/cm2 for other exposures: a. On or about December 10, 2020, an employee was exposed to an electrical hazard when installing lines to new power poles and not wearing a face shield with a minimum arc rating of 8 cal/cm2 to prevent burns to the face, in the event of an arc flash.