Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1502444.015
Citation: 01004
Citation Type: Serious
Abatement Date: 07/12/2021 2
Initial Penalty: $2,926.00
Current Penalty: $1,609.00
Issuance Date: 05/13/2021
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 06/09/2021
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/09/2021 | $1,609.00 | 07/12/2021 | Serious | |
| Penalty | Z: Issued | 05/13/2021 | $2,926.00 | 06/09/2021 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: a)Spray booth: Electrical equipment located at the entry of the spray room, including, but not limited to, a 480 volt electrical panel, light switches and a 120 volt 2x2 receptacle, were not Class 1 Division 2 for hazardous locations observed on or about 11/16/2020. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Translate