Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1489984.015
Citation: 01001
Citation Type: Other
Abatement Date: 10/09/2020 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/29/2020
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): R
Gravity:
Report ID: 0316300
Contest Date:
Final Order: 10/01/2020
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/01/2020 | $0.00 | 10/09/2020 | Other | |
| Penalty | Z: Issued | 09/29/2020 | $0.00 | 10/09/2020 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a) Fire Station #14, Yorktown Naval Weapons Station: On or about 08/25/20, the outdoor outlet, next to the picnic table, was found to not be in accordance with instructions included in the listing or labeling. A statement on the faceplate of the outdoor outlet states, "wet conditions, cover closed". The outlet was not covered with the cover being on the ground below the outlet and filled with water. The outlet was GFCI protected. The outlet was known to be used on 08/19/20 as the power source for the table saw the victim was using.