Violation Detail
Standard Cited: 19260403 I02 I General requirements.
Inspection Nr: 1477942.015
Citation: 01001
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $8,848.00
Current Penalty: $6,193.60
Issuance Date: 09/08/2020
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): R
Gravity: 5
Report ID: 0418300
Contest Date:
Final Order: 09/15/2020
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/15/2020 | $6,193.60 | Serious | ||
| Penalty | Z: Issued | 09/08/2020 | $8,848.00 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph: (a) On or about 06/03/2020 - Cooling Tower Switchgear building, D4 cubicle, the 4000-Volt surge arrester panel did not have a protective cover installed to prevent contact with energized conductors.