Violation Detail
Standard Cited: 19100178 F01 Powered industrial trucks.
Inspection Nr: 1450751.015
Citation: 01006
Citation Type: Serious
Abatement Date: 07/02/2020 2
Initial Penalty: $2,313.00
Current Penalty: $1,156.50
Issuance Date: 06/08/2020
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 1
Report ID: 0418100
Contest Date:
Final Order: 09/01/2020
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/01/2020 | $1,156.50 | 07/02/2020 | Serious | |
| Penalty | Z: Issued | 06/08/2020 | $2,313.00 | 07/02/2020 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.178(f)(1): The storage and handling of liquid fuels such as gasoline and diesel fuel shall be in accordance with NFPA Flammable and Combustible Liquids Code (NFPA No. 30-1969), which is incorporated by reference as specified in Sec. 1910.6. On or about December 11, 2019 at the worksite located at 1331 Lions Club Road in Madison, Georgia outside of the manufacturing building at the portable diesel fuel refilling tank, workers were exposed to fire hazards where the 500 gallon tank was not protected against vehicular contact form traffic including but not limited to the Caterpillar forklift, company vehicles, personal and miscellaneous delivery vehicles during refueling and passing by.