Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
This violation item has been deleted.
Inspection Nr: 1421282.015
Citation: 02002
Citation Type: Other
Abatement Date: 02/19/2020
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/04/2020
Nr Instances: 1
Nr Exposed: 20
Related Event Code (REC):
Gravity:
Report ID: 0627100
Contest Date: 02/24/2020
Final Order: 10/19/2022
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 10/19/2022 | $0.00 | 02/19/2020 | Other | |
Penalty | C: Contested | 03/04/2020 | $0.00 | 02/19/2020 | Other | |
Penalty | Z: Issued | 02/04/2020 | $0.00 | 02/19/2020 | Other |
Text For Citation: 02 Item/Group: 002 Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." On or about August 5, 2019 and times prior, the employer used circuit breakers that were not listed and marked "SWD" as a light switches in the following locations: a. On the southwest corner of Fab 1 workshop. b. On the east wall in Fab 2 workshop.