Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1419924.015
Citation: 01004
Citation Type: Serious
Abatement Date: 05/29/2020 2
Initial Penalty: $2,842.00
Current Penalty: $600.00
Issuance Date: 11/08/2019
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0729700
Contest Date: 12/04/2019
Final Order: 07/24/2020
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 07/24/2020 | $600.00 | 05/29/2020 | Serious | |
| Penalty | C: Contested | 12/11/2019 | $2,842.00 | 12/06/2019 | Serious | |
| Penalty | Z: Issued | 11/08/2019 | $2,842.00 | 12/06/2019 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: Employees were exposed to electrical shock hazards. Employees engaged in operating the Industrial Air Compressor in the Bay door 1 compressor room were exposed to electrical hazards when plugging in the air compressor. The power cord flexible conduit entering the air compressor electrical box was not provided with strain relief.