Violation Detail
Standard Cited: 19100147 C04 II The control of hazardous energy (lockout/tagout).
Inspection Nr: 1402032.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 10/31/2019 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/04/2019
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC): R
Gravity: 5
Report ID: 0418300
Contest Date:
Final Order: 10/28/2019
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/28/2019 | $0.00 | 10/31/2019 | Serious | |
| Penalty | Z: Issued | 10/04/2019 | $0.00 | 10/31/2019 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D): (a) On or about May 09, 2019 - Corn Steaming Area, employees were exposed to electrical and struck-by hazards when lockout/tagout machine specific procedures for equipment, such as the Feeder Flaker and the 120/208 V Flaker Feeder Drive did not specifically describe how to shut down the equipment, how to relieve stored energy, the order that locks were to be installed/removed when multiple locks were required, and how to verify the effectiveness of the energy control measures.
Translate