Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1401508.015
Citation: 01005
Citation Type: Serious
Abatement Date: 08/08/2019 5
Initial Penalty: $2,273.00
Current Penalty: $2,273.00
Issuance Date: 06/25/2019
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity: 1
Report ID: 0419400
Contest Date:
Final Order: 08/20/2019
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 06/25/2019 | $2,273.00 | 08/08/2019 | Serious |
Text For Citation: 01 Item/Group: 005 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed (a) OBS Chop Saw - On or about May 14, 2019, the employer did not ensure that two openings at the side of an energized 240 volt control panel were closed in a heavy wood dust environment, exposing employees electrical and fire hazards.