Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 1401254.015
Citation: 01011
Citation Type: Serious
Abatement Date: 11/18/2019 2
Initial Penalty: $3,978.00
Current Penalty: $2,000.00
Issuance Date: 11/08/2019
Nr Instances: 2
Nr Exposed: 6
Related Event Code (REC):
Gravity: 1
Report ID: 0936400
Contest Date:
Final Order: 12/26/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/26/2019 | $2,000.00 | 11/18/2019 | Serious | |
Penalty | Z: Issued | 11/08/2019 | $3,978.00 | 11/18/2019 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) B Building- Employees were exposed to fire and electrical hazards from material, shelving, and large debris stored within three feet of the electrical cut off switch for the building lights, press and "HB" panel. b) A Building- Employees were exposed to fire and electrical hazards from a storage container located within three feet of a high voltage electrical cabinet.