Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1375672.015
Citation: 01011A
Citation Type: Serious
Abatement Date: 07/25/2019 2
Initial Penalty: $4,508.00
Current Penalty: $2,254.00
Issuance Date: 06/07/2019
Nr Instances: 4
Nr Exposed: 8
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 07/09/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/09/2019 | $2,254.00 | 07/25/2019 | Serious | |
Penalty | Z: Issued | 06/07/2019 | $4,508.00 | 07/25/2019 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Building 6, Electrical Substation: On, or about, April 16, 2019, the following transformers were not installed in accordance with their listing/labeling in that holes had been made in each cover for electrical and, in some instances, ventilation connections: A. Transformer #2: ACME, Catalog No. T-3-53348-3S. B. Transformer #3 and #4: GE, Catalog No. 9T91L2245. C. Transformer #5: Jefferson Electric, Catalog No. 223-0002-947. D. Transformer #6: Jefferson Electric, Catalog No. 223-3317.