Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1340459.015
Citation: 01009
Citation Type: Serious
Abatement Date: 02/12/2019 2
Initial Penalty: $6,251.00
Current Penalty: $5,750.00
Issuance Date: 01/30/2019
Nr Instances: 2
Nr Exposed: 100
Related Event Code (REC): C
Gravity: 1
Report ID: 0627100
Contest Date:
Final Order: 02/28/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/28/2019 | $5,750.00 | 02/12/2019 | Serious | |
Penalty | Z: Issued | 01/30/2019 | $6,251.00 | 02/12/2019 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater: On or about August 9, 2018 and times prior, the employer did not ensure that the following electrical equipment were not blocked/obstructed by items in the workplace: - a. The electrical disconnect box in the Receiving Area 902, South Plant b. The electrical disconnect box in Van Line 3 Area 10, South Plant c. The electrical breaker box in the Suspension Area, South Plant d. The electrical breaker and disconnect boxes in the maintenance shop, North Plant e. The electrical disconnect box by Weld Booth 15, North Plant f. The electrical breaker box by the north exit door in the Quality Hold Loc 040 400, North Plant