Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1326689.015
Citation: 01005D
Citation Type: Serious
Abatement Date: 11/28/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/10/2018
Nr Instances: 2
Nr Exposed: 20
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 10/30/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/30/2018 | $0.00 | 11/28/2018 | Serious | |
Penalty | Z: Issued | 10/10/2018 | $0.00 | 11/28/2018 | Serious |
Text For Citation: 01 Item/Group: 005D Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: A. On or about July 2, 2018, in the following instances, flexible cords had been pulled from their fittings, exposing the energized wiring and exposing employees to electric shock hazards: 1. The 220V cord for the Hyster forklift battery charging unit near the entry to the Bedding Warehouse. 2. The cord for the 120V Dayton dock light at the Loading Dock.