Violation Detail
Standard Cited: 19100303 B06 General.
Inspection Nr: 1326689.015
Citation: 01001B
Citation Type: Serious
Abatement Date: 11/28/2018 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/10/2018
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): C
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 10/30/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/30/2018 | $0.00 | 11/28/2018 | Serious | |
Penalty | Z: Issued | 10/10/2018 | $0.00 | 11/28/2018 | Serious |
Text For Citation: 01 Item/Group: 001B Hazard:
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that had a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures and were not identified for use in the operating environment: A. On or about July 2, 2019, Upholstery Cleaning Area: The upholstery cleaning process was being conducted immediately in front of the 480 electrical main panel. Electrical equipment, including transformers, showed evidence of being splashed by cleaning solution. The base of the cabinet for the 480V electrical main was rusted. The floor drain in the area was clogged, leaving 1/2 inch of standing water. Employees working in the area, standing in water, were exposed to electric shock hazards.