Violation Detail
Standard Cited: 19260416 A01 General requirements.
Inspection Nr: 1288176.015
Citation: 01001A
Citation Type: Serious
Abatement Date: 06/14/2018 2
Initial Penalty: $11,641.00
Current Penalty: $11,641.00
Issuance Date: 05/18/2018
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): R
Gravity: 10
Report ID: 0420600
Contest Date: 06/13/2018
Final Order: 12/31/2018
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 12/31/2018 | $11,641.00 | 06/14/2018 | Serious | |
| Penalty | C: Contested | 06/15/2018 | $11,641.00 | 06/14/2018 | Serious | |
| Penalty | Z: Issued | 05/18/2018 | $11,641.00 | 06/14/2018 | Serious |
Text For Citation: 01 Item/Group: 001A Hazard:
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: (a) Main (existing) electrical room - employees were engaged in pulling and cutting the exposed copper of the three phases and neutral wires while the main switchgear was energized with exposed energized parts at the bottom of the equipment; on or about January 9, 2018.