Violation Detail
Standard Cited: 19100253 B04 III Oxygen-fuel gas welding and cutting.
This violation item has been deleted.
Inspection Nr: 1278986.015
Citation: 01002
Citation Type: Serious
Abatement Date: 05/16/2018
Initial Penalty: $9,239.00
Current Penalty: $0.00
Issuance Date: 03/30/2018
Nr Instances: 1
Nr Exposed: 10
Related Event Code (REC):
Gravity: 5
Report ID: 0729700
Contest Date: 04/20/2018
Final Order: 07/06/2018
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 07/06/2018 | $0.00 | 05/16/2018 | Serious | |
| Penalty | C: Contested | 04/23/2018 | $9,239.00 | 05/16/2018 | Serious | |
| Penalty | Z: Issued | 03/30/2018 | $9,239.00 | 05/16/2018 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: Employees engaged in welding activities located at east wall of weld shop were exposed to fire hazards in that oxygen cylinders were stored next to flammable cylinders containing acetylene. The fire wall which separated the cylinders included a void which resulted in the fire wall not being at least 5 feet high with a fire rating of at least one-half hour.