Violation Detail
Standard Cited: 19100119 D03 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 1277959.015
Citation: 01003
Citation Type: Serious
Abatement Date: 06/20/2018 2
Initial Penalty: $11,641.00
Current Penalty: $6,760.00
Issuance Date: 05/03/2018
Nr Instances: 4
Nr Exposed: 2
Related Event Code (REC):
Gravity: 10
Report ID: 0626600
Contest Date:
Final Order: 05/22/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/22/2018 | $6,760.00 | 06/20/2018 | Serious | |
Penalty | Z: Issued | 05/03/2018 | $11,641.00 | 06/20/2018 | Serious |
Text For Citation: 01 Item/Group: 003 Hazard:
29 CFR 1910.119(d)(3)(i)(D): Process safety information (PSI) pertaining to the equipment in the process did not include relief system design and design basis: On or about November 16, 2017, at the Double R Brand Foods facility located in Lufkin Texas, the employer did not ensure that PSI for relief system design and design basis for the ammonia refrigeration systems and pressure relief/safety valves (PRV/PSV) was included for the following: a. The relief system design and design basis for the ammonia refrigeration systems b. Two (2) PSVs for Re-circulator, V-01 c. Two (2) PSVs for Re-circulator/ Intercooler, V-04 d. Two (2) PSVs for Control Pressure Receiver, V-06