Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 1277959.015
Citation: 01002
Citation Type: Serious
Abatement Date: 06/20/2018 2
Initial Penalty: $8,315.00
Current Penalty: $4,900.00
Issuance Date: 05/03/2018
Nr Instances: 3
Nr Exposed: 2
Related Event Code (REC):
Gravity: 5
Report ID: 0626600
Contest Date:
Final Order: 05/22/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/22/2018 | $4,900.00 | 06/20/2018 | Serious | |
Penalty | Z: Issued | 05/03/2018 | $8,315.00 | 06/20/2018 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams (P&ID) were not accurate: On or about November 16, 2017, at the Double R Brand Foods facility located in Lufkin Texas, the employer did not ensure that piping and instrument diagrams (P&IDs) were accurate. The P&IDs were not accurate as the following but not limited to. a. P&ID-101, Rev. #0 (Date:12/24/01). This P&ID did not include relief valves and detail configurations of the high stage compressors HS-5 and HS-6. b. P&ID-102, Rev. #0 (Date:12/24/01). This P&ID did not include detail configurations of the evaporative condenser EC-4. c. P&ID-101/102/103 Rev. #0 (Date:12/24/01). These P&IDs did not include ammonia vent-lines or stacks for the high stage compressors HS-5 and HS-6.