Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1225248.015
Citation: 01004A
Citation Type: Serious
Abatement Date: 10/12/2017 2
Initial Penalty: $5,975.00
Current Penalty: $4,481.25
Issuance Date: 10/11/2017
Nr Instances: 2
Nr Exposed: 2
Related Event Code (REC):
Gravity: 1
Report ID: 0625400
Contest Date:
Final Order: 11/03/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/03/2017 | $4,481.25 | 10/12/2017 | Serious | |
Penalty | Z: Issued | 10/11/2017 | $5,975.00 | 10/12/2017 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910. On or about 12 April 2017, and at times prior thereto, electrical panels and components were blocked by items in front of them reducing safe and ready access, exposing the employees to electrical, tripping and struck by hazards. a) Maintenance Shop: Maintenance employees that are required to reset breakers at least two times per month have restricted access where various items are stored within 3 feet of the breaker panel. b) Production Floor: Near the Break Room door, several electrical components were blocked by a rolling table for access. Items such as a transformer, disconnect switch, and a breaker panel.