Violation Detail
Standard Cited: 19100137 C02 II Electrical protective equipment.
Inspection Nr: 1214657.015
Citation: 01002A
Citation Type: Serious
Abatement Date: 10/05/2017 2
Initial Penalty: $5,926.00
Current Penalty: $1,000.00
Issuance Date: 08/18/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0523400
Contest Date: 09/13/2017
Final Order: 03/09/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/09/2018 | $1,000.00 | 10/05/2017 | Serious | |
Penalty | C: Contested | 09/15/2017 | $5,926.00 | 10/05/2017 | Serious | |
Penalty | Z: Issued | 08/18/2017 | $5,926.00 | 10/05/2017 | Serious |
Text For Citation: 01 Item/Group: 002A Hazard:
29 CFR 1910.137(c)(2)(ii): Insulating equipment shall be inspected for damage before each day's use and immediately following any incident that can reasonably be suspected of causing damage. Insulating gloves were not given an air test, along with the inspection. (a) Maintenance employee used Salisbury rubber insulating gloves, Class 00, Type I gloves rated to 500 volts AC when working on energized circuits without performing an air test on gloves before each use. This exposed the employee to an electrical shock hazard.