Violation Detail
Standard Cited: 19100106 E09 I Flammable liquids.
Inspection Nr: 1210448.015
Citation: 01001
Citation Type: Serious
Abatement Date: 06/19/2017 2
Initial Penalty: $6,157.00
Current Penalty: $3,694.20
Issuance Date: 05/23/2017
Nr Instances: 2
Nr Exposed: 10
Related Event Code (REC): R
Gravity: 5
Report ID: 0418300
Contest Date:
Final Order: 06/08/2017
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 06/08/2017 | $3,694.20 | 06/19/2017 | Serious | |
| Penalty | Z: Issued | 05/23/2017 | $6,157.00 | 06/19/2017 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1910.106(e)(9)(i): Maintenance and operating practices were not in accordance with established procedures which will tend to control leakage and prevent the accidental escape of flammable liquids: a. On or about 2/7/17 - PE-X laboratory; A quality control test which utilized xylene, a flammable liquid, was conducted in a laboratory hood without an operating exhaust fan. b. On or about 2/7/17 - PE-X laboratory; The laboratory hood was not equipped with a flow indicator to alert users to improper exhaust flow.